Operating principle and connection to safety control units

PDF in English, R1 editorial revision of 20/10/2026, 1 page: text and connection diagrams, with the brown–yellow conductor pair stated correctly. It does not replace the applicable manuals or safety-function verification.

Archived original document: Operating principle of the safety elements (PDF, 2024); the R1 revision corrects the conductor designation.

Operating principle of WIDE pressure-sensitive elements and connection to the safety control unit
Wiring diagram of pressure-sensitive elements connected to a WIDE safety control unit

The continuity of the sensitive elements is monitored by checking the electrical continuity between the conductors respectively white-green and brown-yellow.

If an interruption occurs between the white-green and/or brown-yellow conductors, the safety control unit reacts by opening the contacts of the safety relays (which are normally closed).

The sensitive element behaves like a normally open contact. The pressure of the sensitive element causes a closing of the contact with consequent closure of the circuit between all 4 conductors.

It is possible to put multiple elements in cascade, using the following scheme.

Several pressure-sensitive elements connected in cascade to a single safety control unit