OSSD stands for Output Signal Switching Device: it is an electronic safety output, solid-state, that not only switches but continuously checks that it is still able to switch. You find it on the output side of a safety control unit — a light curtain, a laser scanner, a safety module — heading towards the machine logic.
In the world of pressure-sensitive devices the acronym causes one recurring confusion, and clearing it up is what this page is for: OSSD describes what leaves the control unit, not what enters it from the sensor.
What an OSSD output does that a contact does not
A conventional electromechanical contact says “I am open” or “I am closed”. Until something tests it, there is no way to know whether it is still able to open: a welded contact keeps reporting its state long after it has lost the ability to change it.
An OSSD output monitors itself and its own wiring. If it detects an abnormal condition — a short circuit between the two channels, or towards the supply — it drives the outputs to the safe state without waiting for the next demand. It is this continuous self-diagnosis, not the technology as such, that sets it apart.
OSSD outputs normally come in pairs and work together: the redundancy exists so that a failure in one channel does not remove the safety function.
Test pulses: what they are for
To verify channel integrity, OSSD outputs carry short test pulses superimposed on the signal. During a pulse the output switches for a very short time and the circuit checks that the switching actually happens.
This is why connecting an OSSD output to an input that is not designed for it — a standard PLC, a general-purpose relay, an unfiltered input — can produce trips that look inexplicable: the input reads the test pulses as state changes.
Pulse duration, frequency, phase shift and current are not specified in the public documentation of our products, and we do not report them here. If you need to interface the output to a particular machine logic, ask for them explicitly at design stage: they are integration data, not a detail.
OSSD is the unit’s output, not the sensor’s signal
This is the point that justifies the page, and the most common misunderstanding among people searching for “OSSD”.
A safety mat, a safety edge or a safety bumper is a passive device: it changes an electrical quantity when someone presses it, and nothing else. It does not diagnose, does not switch a safety circuit, does not notice its own failure.
Upstream of the unit, then, the device does not speak “in OSSD”. It speaks one of the two languages of its wiring: 4-wire contacts on two channels, or a 2-wire circuit with a termination resistor. The OSSD signal is born downstream, inside the control unit.
Anyone looking for “an OSSD sensor” and expecting the mat to produce that signal directly is looking for the wrong thing. The useful question is a different one: which control unit does this device need, and which output type do I need towards the machine?
OSSD, relay contacts and the control unit: three different things
These are three distinct levels, and it is worth keeping them apart.
- The safety control unit — module, or safety control module — is the device. It receives the signal from the pressure-sensitive element, interprets it, monitors itself and commands the stop.
- Relay outputs with forcibly guided contacts are one way of building the unit’s safety output: physical contacts, with a mechanical linkage that prevents a normally open and a normally closed contact from being closed at the same time.
- OSSD outputs are the other way: electronic, solid-state, self-diagnosing.
Neither is better in absolute terms. Relay contacts carry higher voltages and currents and interface with any logic; OSSD outputs have no mechanical wear, switch faster and diagnose the wiring, but they require inputs designed to receive them.
Both live in our range of safety control units: four units have relay outputs with forcibly guided contacts — WACS-24R, NC95, NC96 MAT and WARL24-2A — and one has OSSD semiconductor outputs, the WASS-1224.
And what about “safety relays”?
Most people searching for a safety relay have something specific in mind: a general-purpose safety logic module, DIN-rail mounted, that accepts inputs from any device and is sold from a catalogue. Ask “how does a safety relay work” and the answer you get is about that class of product.
Our units are something else: they are dedicated to pressure-sensitive devices. They read a specific signal — resistive, or dual-contact — that a general-purpose module is not designed to interpret. The distinction is not “relay or not relay”: it is general-purpose versus dedicated.
So if you arrived here looking for a safety relay and you have to connect a mat, an edge or a bumper, the term that will actually find what you need is safety control unit, or safety module for pressure-sensitive devices.
How a pressure-sensitive device is connected
Upstream of the unit there are two documented ways, and the choice is not neutral.
4-wire contact, two channels. The device opens or closes two independent circuits. This is the connection used by the Standard series edges, which the datasheets in revision 01-04-2026 declare compatible with all five of our units.
Two wires with an 8.2 kΩ termination resistor. A single circuit, in which the unit distinguishes rest, actuation and fault by reading the resistance value. This is the connection used by the COE series edges, which the datasheet declares compatible with WACS-24R and WASS-1224: the other three units are not listed, and we do not add them by analogy.
On the WASS-1224 the thresholds stated in the manual are above 13.8 kΩ and below 3.8 kΩ. This is why cable length is not a logistical detail: it affects line resistance and therefore threshold recognition in 2-wire circuits.
A note on compatibility. The combinations listed above are those explicitly declared in published documents. For mats, the explicitly documented pairing is the one with the WASS-1224; for the bumper there is no public datasheet declaring compatible units. Combinations that are not documented are not “forbidden”: they are to be confirmed case by case with our technical department, and we do not declare them here. The maximum number of elements that can be connected in series, where stated, is ten: it applies to the Standard series and to the COE series on WACS-24R and WASS-1224, and it must not be extended to the other units.
When you need an OSSD output
Three typical situations where the electronic output is the natural choice:
- the downstream machine logic has safety inputs designed to receive it, as safety PLCs and many drives do;
- the expected number of operations is high and you want to avoid contact wear;
- you want the wiring towards the machine to be monitored, not merely switched.
Relay contacts remain preferable in other cases: voltages or currents beyond the reach of an electronic output, interfacing with logic that is not designed for OSSD, or simply an existing installation that already uses them.
One last warning, because it is a mistake we see often: some units have an auxiliary output for signalling. It is not a safety output and must not be placed in the safety chain, however convenient that may look.
Why the output alone is not enough: the Performance Level belongs to the chain
One final clarification, because it follows directly from all of the above. The fact that a unit has OSSD outputs does not by itself assign it a Performance Level, and it certainly does not assign one to the sensor you connect to it.
The WASS-1224 itself documents Category 1 and PL c with a 2-wire device, and Category 3 and PL e with a 4-wire device or a 2-wire device in category 3. Same unit, same OSSD outputs, two levels apart: what changes is the wiring. The full reasoning is in our guide to Performance Level and ISO 13849-1.
In short
- OSSD = a self-diagnosing solid-state safety output, sitting on the output side of the control unit.
- A pressure-sensitive device does not produce an OSSD signal: it is passive and connects with 2 or 4 wires.
- OSSD outputs and relay outputs with forcibly guided contacts are two ways of building the safety output of the same unit.
- Test pulse parameters are not published: ask for them at design stage.
- Compatibility holds only where it is declared: everything else is confirmed case by case.
Wiring schemes between pressure-sensitive elements and control units are collected in the dedicated technical sheet.